Comportamento de malhas de aterramento de subestação de energia frente a descargas atmosféricas: ênfase na avaliação de técnicas de melhoria do desempenho impulsivo por meio de múltiplos pontos de injeção de corrente

dc.contributor.advisorAlípio, Rafael Silva
dc.contributor.advisorLatteshttp://lattes.cnpq.br/6715701375569983
dc.contributor.authorSegantini, Renan Campos
dc.contributor.referee1Rafael Silva Alípio
dc.contributor.referee2Marco Aurélio de Oliveira Schroeder
dc.contributor.referee3Cláudia Rejane de Mesquita
dc.contributor.referee4Miguel de Brito Guimarães Neto
dc.date.accessioned2023-06-26T13:35:50Z
dc.date.available2023-06-26T13:35:50Z
dc.date.issued2018-12-11
dc.description.abstractAs malhas de aterramento, arranjo de eletrodos comumente utilizado em subestações de energia elétrica, que em geral assumem grandes dimensões, são projetadas segundo normas vigentes que levam em consideração apenas solicitações de baixa frequência. No entanto, essas malhas podem ser submetidas a correntes impulsivas advindas de descargas atmosféricas que incidem em cabos de blindagem de linhas próximas à subestação ou mesmo diretamente na subestação. Nesse caso, é importante a adoção de técnicas complementares ao projeto da malha para solicitações lentas, com o intuito de adequar o seu desempenho também a fenômenos impulsivos. Este trabalho se dedica ao estudo do comportamento impulsivo de malhas de aterramento de subestação e à proposição de técnicas de melhoria do desempenho de tais malhas frente a correntes de descargas atmosféricas. Utilizou-se uma modelagem computacional para malhas de aterramento que inclui a dependência da frequência dos parâmetros elétricos do solo, os fenômenos de propagação, os acoplamentos eletromagnéticos e adicionalmente, que permite a injeção simultânea de corrente em distintos nós da malha. A partir da aplicação desse modelo, gera-se ume extenso conjunto de resultados do comportamento impulsivo de uma malha típica de aterramento de subestação. De acordo com os resultados, o desempenho impulsivo da malha é sensivelmente influenciado pelo ponto de injeção de corrente: quanto maior a área efetiva no entorno do ponto de injeção, melhor é o desempenho impulsivo. Mostra-se que a distribuição da corrente de descarga por meio de múltiplas terminações de terra melhora de forma significativa o desempenho impulsivo da malha de aterramento.
dc.description.abstractotherThe grounding grids, arrangement of electrodes commonly used in electrical power substations, which generally assume large dimensions, are designed according to Standards which take into account only slow occurrences. However, such grounding grids can be subjected to impulse currents associated with lightning that might strike shielding wires of lines near the substation or even directly in the substation. In this case, it is important to adopt complementary techniques in order to improve the impulse performance of the grounding grid. This work is dedicated to the study of the impulse behavior of substation grounding grids and the proposition of techniques to improve their impulse performance. To this aim, a computational model for simulating grounding grids is developed, including the frequency dependence of electrical parameters of soil, propagation phenomena, electromagnetic couplings and, in addition, the possibility of simultaneous injection of current into distinct nodes of the grid. From the application of the developed model, an extensive set of results of the impulse behavior of a typical substation grounding grid is obtained. According to the results, the impulse performance of the grid strongly depends on the current injection point: the larger the effective area around the injection point, the better the impulse performance. It is shown that the distribution of the lightning current through multiple earth terminations significantly improves the impulse performance of the grounding grid.
dc.identifier.urihttps://repositorio.cefetmg.br/handle/123456789/334
dc.language.isopt
dc.publisherCentro Federal de Educação Tecnológica de Minas Gerais / Universidade Federal de São João del-Rei
dc.publisher.countryBrasil
dc.publisher.initialsCEFET-MG / UFSJ
dc.publisher.programPrograma de Pós-Graduação em Engenharia Elétrica
dc.subjectAterramento elétrico
dc.subjectEnergia elétrica
dc.subjectDescargas atmosféricas
dc.subjectLinhas elétricas - Transmissão
dc.titleComportamento de malhas de aterramento de subestação de energia frente a descargas atmosféricas: ênfase na avaliação de técnicas de melhoria do desempenho impulsivo por meio de múltiplos pontos de injeção de corrente
dc.typeThesis
dspace.entity.type

Arquivos

Pacote Original
Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
Comportamento de malhas de aterramento de subestacao de energia frente a descargas atmosfericas_Dissertacao.pdf
Tamanho:
14.36 MB
Formato:
Adobe Portable Document Format
Licença do Pacote
Agora exibindo 1 - 1 de 1
Nenhuma Miniatura disponível
Nome:
license.txt
Tamanho:
1.71 KB
Formato:
Item-specific license agreed to upon submission
Descrição: