Comportamento de malhas de aterramento de subestação de energia frente a descargas atmosféricas: ênfase na avaliação de técnicas de melhoria do desempenho impulsivo por meio de múltiplos pontos de injeção de corrente
dc.contributor.advisor | Alípio, Rafael Silva | |
dc.contributor.advisorLattes | http://lattes.cnpq.br/6715701375569983 | |
dc.contributor.author | Segantini, Renan Campos | |
dc.contributor.referee1 | Rafael Silva Alípio | |
dc.contributor.referee2 | Marco Aurélio de Oliveira Schroeder | |
dc.contributor.referee3 | Cláudia Rejane de Mesquita | |
dc.contributor.referee4 | Miguel de Brito Guimarães Neto | |
dc.date.accessioned | 2023-06-26T13:35:50Z | |
dc.date.available | 2023-06-26T13:35:50Z | |
dc.date.issued | 2018-12-11 | |
dc.description.abstract | As malhas de aterramento, arranjo de eletrodos comumente utilizado em subestações de energia elétrica, que em geral assumem grandes dimensões, são projetadas segundo normas vigentes que levam em consideração apenas solicitações de baixa frequência. No entanto, essas malhas podem ser submetidas a correntes impulsivas advindas de descargas atmosféricas que incidem em cabos de blindagem de linhas próximas à subestação ou mesmo diretamente na subestação. Nesse caso, é importante a adoção de técnicas complementares ao projeto da malha para solicitações lentas, com o intuito de adequar o seu desempenho também a fenômenos impulsivos. Este trabalho se dedica ao estudo do comportamento impulsivo de malhas de aterramento de subestação e à proposição de técnicas de melhoria do desempenho de tais malhas frente a correntes de descargas atmosféricas. Utilizou-se uma modelagem computacional para malhas de aterramento que inclui a dependência da frequência dos parâmetros elétricos do solo, os fenômenos de propagação, os acoplamentos eletromagnéticos e adicionalmente, que permite a injeção simultânea de corrente em distintos nós da malha. A partir da aplicação desse modelo, gera-se ume extenso conjunto de resultados do comportamento impulsivo de uma malha típica de aterramento de subestação. De acordo com os resultados, o desempenho impulsivo da malha é sensivelmente influenciado pelo ponto de injeção de corrente: quanto maior a área efetiva no entorno do ponto de injeção, melhor é o desempenho impulsivo. Mostra-se que a distribuição da corrente de descarga por meio de múltiplas terminações de terra melhora de forma significativa o desempenho impulsivo da malha de aterramento. | |
dc.description.abstractother | The grounding grids, arrangement of electrodes commonly used in electrical power substations, which generally assume large dimensions, are designed according to Standards which take into account only slow occurrences. However, such grounding grids can be subjected to impulse currents associated with lightning that might strike shielding wires of lines near the substation or even directly in the substation. In this case, it is important to adopt complementary techniques in order to improve the impulse performance of the grounding grid. This work is dedicated to the study of the impulse behavior of substation grounding grids and the proposition of techniques to improve their impulse performance. To this aim, a computational model for simulating grounding grids is developed, including the frequency dependence of electrical parameters of soil, propagation phenomena, electromagnetic couplings and, in addition, the possibility of simultaneous injection of current into distinct nodes of the grid. From the application of the developed model, an extensive set of results of the impulse behavior of a typical substation grounding grid is obtained. According to the results, the impulse performance of the grid strongly depends on the current injection point: the larger the effective area around the injection point, the better the impulse performance. It is shown that the distribution of the lightning current through multiple earth terminations significantly improves the impulse performance of the grounding grid. | |
dc.identifier.uri | https://repositorio.cefetmg.br/handle/123456789/334 | |
dc.language.iso | pt | |
dc.publisher | Centro Federal de Educação Tecnológica de Minas Gerais / Universidade Federal de São João del-Rei | |
dc.publisher.country | Brasil | |
dc.publisher.initials | CEFET-MG / UFSJ | |
dc.publisher.program | Programa de Pós-Graduação em Engenharia Elétrica | |
dc.subject | Aterramento elétrico | |
dc.subject | Energia elétrica | |
dc.subject | Descargas atmosféricas | |
dc.subject | Linhas elétricas - Transmissão | |
dc.title | Comportamento de malhas de aterramento de subestação de energia frente a descargas atmosféricas: ênfase na avaliação de técnicas de melhoria do desempenho impulsivo por meio de múltiplos pontos de injeção de corrente | |
dc.type | Thesis | |
dspace.entity.type |
Arquivos
Pacote Original
1 - 1 de 1
Carregando...
- Nome:
- Comportamento de malhas de aterramento de subestacao de energia frente a descargas atmosfericas_Dissertacao.pdf
- Tamanho:
- 14.36 MB
- Formato:
- Adobe Portable Document Format
Licença do Pacote
1 - 1 de 1
Nenhuma Miniatura disponível
- Nome:
- license.txt
- Tamanho:
- 1.71 KB
- Formato:
- Item-specific license agreed to upon submission
- Descrição: